Size a circuit protective conductor with the adiabatic equation, S = √( I²t ) ÷ k.
When the protective conductor is smaller than the line conductor and you need to show it can withstand the fault, or when the tabulated sizes do not apply. It is the check behind a reduced csa protective conductor.
A soldered or clamped joint can lower the permissible k because of the joint temperature limit. Use the value for your conductor and joint from BS 7671 Table 43.1.
Mantle is free for UK gas and electrical engineers: CP12 gas safety certificates, service records, customer reminders and field calculators in your pocket. Get started.
This calculator is a design and field aid, not a substitute for BS 7671, the IET Guidance Notes, or the manufacturer’s instructions. Where they disagree, the standard and the maker’s data win. Always work to the current edition.