Adiabatic equation calculator

Size a circuit protective conductor with the adiabatic equation, S = √( I²t ) ÷ k.

How it works

  1. Enter the earth fault current and the disconnection time the protective device achieves at that current.
  2. Pick the conductor material and insulation to set k: copper PVC 115, copper XLPE/EPR 143, aluminium PVC 76, aluminium XLPE 94, steel PVC 51, steel XLPE 46.
  3. Mantle gives the minimum csa and the next standard size up. The adiabatic check is one of the conditions for a protective conductor — the tabulated rules in the regs often settle it, and the value of k for your exact joint may differ.

Common questions

When do I use the adiabatic equation?

When the protective conductor is smaller than the line conductor and you need to show it can withstand the fault, or when the tabulated sizes do not apply. It is the check behind a reduced csa protective conductor.

Which k do I use for a joint?

A soldered or clamped joint can lower the permissible k because of the joint temperature limit. Use the value for your conductor and joint from BS 7671 Table 43.1.

Want the certificates, reminders and the full Tool Box?

Mantle is free for UK gas and electrical engineers: CP12 gas safety certificates, service records, customer reminders and field calculators in your pocket. Get started.

Other free electrical calculators

This calculator is a design and field aid, not a substitute for BS 7671, the IET Guidance Notes, or the manufacturer’s instructions. Where they disagree, the standard and the maker’s data win. Always work to the current edition.