Power factor calculator

Work out kVA, kVAr and phase angle, and the correction needed to reach a target power factor.

How it works

  1. Enter the real power in kW and the present power factor. Mantle gives the apparent power in kVA, the reactive power in kVAr and the phase angle.
  2. Set a target power factor to see how much correction in kVAr brings the installation up to it. Correction kVAr = kW × ( tan φ₁ − tan φ₂ ).
  3. Lower power factors draw more current for the same real power, which costs capacity and, on larger supplies, money. Size correction equipment to at least the figure shown and let the supplier design the final scheme.

Common questions

What is a good power factor?

The closer to 1, the better. Many supplies aim for 0.95 or above, and some tariffs give a discount for keeping it there.

Can I over-correct?

Yes. Leading power factor from too much capacitance causes its own problems. Do not add more than the calculation calls for, and use switched stages on varying loads.

Want the certificates, reminders and the full Tool Box?

Mantle is free for UK gas and electrical engineers: CP12 gas safety certificates, service records, customer reminders and field calculators in your pocket. Get started.

Other free electrical calculators

This calculator is a design and field aid, not a substitute for BS 7671, the IET Guidance Notes, or the manufacturer’s instructions. Where they disagree, the standard and the maker’s data win. Always work to the current edition.