Cable voltage drop calculator

Work out the volt drop on a circuit and check it against the BS 7671 limits.

How it works

  1. Enter the design current and the cable length, then pick a typical cable or type the mV/A/m value from your BS 7671 tables.
  2. Vd = mV/A/m × Ib × L ÷ 1000. Mantle shows the drop in volts and as a percentage of the supply voltage.
  3. It compares the result with the usual limits: 3% for lighting and 5% for other uses. For three-phase circuits take the mV/A/m from the three-phase column of the tables and use the same formula.

Common questions

Where do the typical cable values come from?

Flat twin & earth copper conductors at 70 °C, single-phase column. They are a convenience only — confirm the value for your cable, installation method and temperature in the regs tables.

Does the limit include the whole circuit?

The percentage applies from the origin of the installation to the furthest point of the circuit, including any distribution circuit. Sum the drops where a circuit runs through more than one cable.

Want the certificates, reminders and the full Tool Box?

Mantle is free for UK gas and electrical engineers: CP12 gas safety certificates, service records, customer reminders and field calculators in your pocket. Get started.

Other free electrical calculators

This calculator is a design and field aid, not a substitute for BS 7671, the IET Guidance Notes, or the manufacturer’s instructions. Where they disagree, the standard and the maker’s data win. Always work to the current edition.