Maximum Zs calculator

Look up the maximum earth fault loop impedance for an MCB or RCBO, and check a measured reading.

How it works

  1. Pick the device type and rating. Max Zs = U₀ ÷ ( curve factor × In ), using a curve factor of 5 for type B, 10 for type C and 20 for type D.
  2. The design value assumes the conductors are at their operating temperature. When you measure Zs with the installation cold or at ambient, compare the reading with 80% of the design value.
  3. Type a measured Zs to see at once whether it passes. The table below lists the design-temperature values for standard ratings.

Common questions

Does this cover fuses?

No. Fuses and MCCBs to BS 88, and BS 3036 rewirable fuses, have their own tabulated values because the operating current does not follow the same simple multiple. Use the BS 7671 tables for those.

Why the 80% figure?

The tabulated maximum assumes the conductor is hot, which raises its resistance. A measured reading taken at ambient is lower for the same installation, so the rule of thumb compares it against 80% of the tabulated value.

Want the certificates, reminders and the full Tool Box?

Mantle is free for UK gas and electrical engineers: CP12 gas safety certificates, service records, customer reminders and field calculators in your pocket. Get started.

Other free electrical calculators

This calculator is a design and field aid, not a substitute for BS 7671, the IET Guidance Notes, or the manufacturer’s instructions. Where they disagree, the standard and the maker’s data win. Always work to the current edition.