Prospective fault current calculator

Work out the prospective short-circuit and earth fault current from the loop impedance.

How it works

  1. Enter the nominal voltage and the loop impedance at the origin — the external loop impedance Ze, or the earth fault loop impedance Zs where that is what you have.
  2. PFC = U₀ ÷ Z. On a TN system the prospective short-circuit current and the prospective earth fault current are both taken this way; the value that matters for the installation is the higher of the two.
  3. Compare the result with the rated short-circuit capacity of the protective devices and the supply equipment. On a TT system the earth fault current is limited by the electrode and is far lower, so take the short-circuit value from the phase-to-neutral loop.

Common questions

Is PFC the same as PSCC?

Often used together. PSCC is the prospective short-circuit current between live conductors; PEFC is the prospective earth fault current to earth. On a TN system they are usually close, and the installation PFC is the higher.

What if I measured the fault current already?

Divide the nominal voltage by the measured current to get the impedance that produced it, then compare that with the device limits.

Want the certificates, reminders and the full Tool Box?

Mantle is free for UK gas and electrical engineers: CP12 gas safety certificates, service records, customer reminders and field calculators in your pocket. Get started.

Other free electrical calculators

This calculator is a design and field aid, not a substitute for BS 7671, the IET Guidance Notes, or the manufacturer’s instructions. Where they disagree, the standard and the maker’s data win. Always work to the current edition.